product overview
Used for monitoring sealed containersSF6The density of gas can be displayed on site, and an alarm will be triggered when the density value reaches the set value. It is suitable for detecting high-pressure systems. We can provide various solutions such as supporting new substations and intelligent transformation of existing substations.
Application scope
SF6Insulated composite electrical appliances(GIS)
SF6Insulated Circuit Breaker
SF6Insulated pole switch
SF6insulating transformer
SF6Insulation Transformer
SF6Insulated busbar system
Product Features
1. Using gas compensation for higher set point accuracy
2. full scale1Level precision display.
3. Suitable for different installation needs indoors and outdoors
4. Micro switch, capable of freely switching between normally open and normally closed points
5. Up to four pairs of nodes, capable of achieving dual alarm and dual lockingWaiting for multiple options for safer and more reliable monitoring
6. High seismic resistance
7. No need for oil filling, no oil leakage hazard
8. Normally closed contacts will not give false alarms due to vibration
Technical Parameter
1. Measurement range:-0.1~0.9MPa
2. Set point accuracy:1Grade(±10 kPa)@ –30...+50 °C
3. Indication accuracy:1Grade(±10 kPa)@ 20 °C
4. Protection level:IP65
5. Working temperature:-40°C~ +60°C,Relative humidity ≤95%RH
6. Leakage rate: ≤1×10-9 Pa·m3/s(Helium leak detection)
7. Interface size:M20×1.5(Customizable)
8. Installation method: radial or axial
9. Electrical connection:Connect the plug when it is pluggable, wire diameter0.2...2.5 mm2
10. Insulation performance: Insulation resistance:>100 MW(DC 500V)
Power frequency withstand voltage:2kV, 50/60 Hz, 1min
11. Contact type: Micro switch
12. Impact level:50g
13. Contact electrical parameters:30W/50VA, 1A.(Maximum)
220VDC/380V 50/60Hz(maximum)
14. Table glass: multi-layer safety glass
15. Weight:1.0kg
16. Pressure sensing components: imported corrugated tube and Bowden tube
Optional features:
measuring range
A wider temperature range:-60°C~+60°C
detectableSF6、Air、N2、SF6+N2Waiting for gas
Remote transmission function