product name:
|
Electric regulating ball valve
|
Product model:
|
ZHJQ
|
|
Drive mode:
|
electric
|
Connection form:
|
Flange type, threaded type
|
|
structural style:
|
Straight through type
|
Sealing material:
|
PTFE/flexible graphite
|
|
Pressure range:
|
1.6~6.4MPa
|
Nominal Diameter:
|
DN15-DN300
|
|
Common materials:
|
Carbon steel, stainless steel
|
technical advice:
|
|
1、 Product Overview
Electric regulating ball valveIt is composed of HQ type intelligent electric actuator and two-way ball valve body, suitable for two position cutting and adjustment occasions. The actuator can be domestic or imported, and adopts an integrated structure,electric actuatorBuilt in servo system, input control signal (4-20mADC or 1-5VDC) and single-phase power supply can control the operation. The intelligent electric ball valve has strong functions, small size, lightweight and pleasant, reliable performance, simple matching, large flow capacity, and is particularly suitable for occasions where the medium is viscous, contains particles, or fibers. currentlyElectric regulating ball valveWidely used in industrial automatic control systems in industries such as food, environmental protection, light industry, petroleum, papermaking, chemical engineering, teaching and research equipment, and power.
2、 Main technical parameters of electric regulating ball valve
valve body
|
Valve body form
|
Direct cast ball valve
|
|
Nominal diameter
|
DN15~300mm
|
|
nominal pressure
|
PN1.6、2.5、4.0、6.4 MPa; ANSI 150、300LB ; JIS 10、20、30K
|
|
Flange standard
|
JIS, ANSI, GB, JB, HG, etc
|
|
Connection form
|
Flange type, threaded type
|
|
Valve cover form
|
Integrated
|
|
Cover type
|
Compression type
|
|
Sealing packing
|
V-shaped polytetrafluoroethylene packing, flexible graphite packing, etc
|
trim
|
Valve core form
|
O-ring valve core
|
|
Traffic characteristics
|
Approximate quick opening type
|
actuator
|
Model of actuator
|
DSR、3810R、DZW、HQ、PSQ
|
|
Main technical parameters
|
Power supply voltage: 220V/50Hz, 380V/50Hz, input signal: 4-20mA or 1-5V-DC, output signal: 4-20mA · DC
|
|
Protection level: equivalent to IP65 (or IP67), explosion-proof mark: Exd Ⅱ BT4, manual operation function: handle
|
|
Environmental temperature: -25~+70 ℃, environmental humidity: ≤ 95%
|
Note: For detailed actuator parameters, please visit the electric actuator page for reference.
3、 Main performance indicators of electric regulating ball valve
|
Nominal diameter DN (mm)
|
15
|
20
|
25
|
32
|
40
|
50
|
65
|
80
|
100
|
125
|
150
|
200
|
250
|
300
|
|
Rated flow coefficient KV
|
21
|
38
|
72
|
112
|
170
|
273
|
384
|
512
|
940
|
1452
|
2222
|
3589
|
5128
|
7359
|
|
Allowable pressure difference (MPa)
|
≤ nominal pressure
|
|
Operating range
|
0-90 °, 0-360 °
|
|
Leakage quantity Q
|
According to GB/T4213-92, less than 0.01% of rated KV
|
|
Basic error
|
±1%
|
|
return difference
|
±1%
|
|
dead zone
|
≤ 1% (adjustable)
|
|
Adjustable range
|
250:1
|
350:1
|
4、 Main component materials of electric regulating ball valve
|
1
|
Left valve body
|
WCB、CF8、CF8M、CF3M
|
|
|
2
|
Right valve body
|
WCB、CF8、CF8M、CF3M
|
|
3
|
valve seat
|
PEFE、PPL、304、316
|
|
4
|
sphere
|
2Cr13、304、316
|
|
5
|
valve stem
|
2Cr13、304、316
|
|
6
|
Packing
|
PTFE/flexible graphite
|
|
7
|
Packing gland
|
WCB、CF8、CF8M、CF3M
|
5、 Main appearance and connection dimensions of electric regulating ball valve

|
Nominal diameter DN (mm)
|
15
|
20
|
25
|
32
|
40
|
50
|
65
|
80
|
100
|
125
|
150
|
200
|
250
|
300
|
|
L
|
130
|
140
|
150
|
165
|
180
|
200
|
220
|
250
|
280
|
320
|
360
|
400
|
630
|
750
|
|
H
|
44.5
|
49
|
55
|
65
|
65
|
75
|
90
|
95
|
115
|
127
|
140
|
172.5
|
310
|
350
|
|
H1
|
Depending on the model of the actuator provided
|
|
D
|
95
|
105
|
115
|
140
|
150
|
165
|
185
|
200
|
220
|
250
|
285
|
340
|
405
|
460
|
|
D1
|
65
|
75
|
85
|
100
|
110
|
125
|
145
|
160
|
180
|
210
|
240
|
295
|
355
|
410
|
|
D2
|
46
|
56
|
65
|
76
|
84
|
99
|
118
|
132
|
156
|
184
|
211
|
266
|
319
|
370
|
|
n-φd
|
4-14
|
4-14
|
4-14
|
4-18
|
4-18
|
4-18
|
4-18
|
8-18
|
8-18
|
8-18
|
8-22
|
12-22
|
12-26
|
12-26
|
|
A、A1
|
Depending on the required torque of the valve, the configuration model and external dimensions vary
|
Note: The above parameters are based on PN1.6MPa. For other pressure levels, please consult the company's technical department. The dimensions in the table do not include standard attachment data. Additionally, due to product improvement and technological innovation parameters, there may be some changes. Please consult the company's technical department for the latest data.