Introduction: Electric pneumatic valve positionerYT-1000RIt is a method of receiving 4-20M DC current signals from a controller or control system, A device that delivers air to the angular stroke pneumatic actuator to control the opening of the valve.
Characteristics of YT-1000R locator: 1. No resonance phenomenon within the range of 5-200Hz; 2. For positive and negative effects, there is a convenient transition between single and double effects; 3. For the vibration generated by small actuators, it can be solved by reducing the throttle hole of the locator; 4. Low air consumption and good economy, 5. It is possible to achieve split range control within 1/2 range without replacing parts. YT-1000R Electrical Valve Positioner Model Rules and Parameters
|
|
Order code: YT-1000RDn1 3 2 S0 1
|
|
model
|
Type of action
|
Explosion-proof rating
|
Feedback lever
|
throttle orifice
|
connection type
|
ambient temperature
|
Option 1
|
Option 2
|
|
YT-1000R
|
Ssingle-acting
|
mExdmIIBT5
|
1 M6x34L
|
1 φ1
|
1 PT
|
S-20℃-70℃
|
0 Standard indicator
|
0 none
|
|
|
Ddouble-acting
|
cExdmIICT5
|
2 M6x63L
|
2 φ2
|
2 NPT
|
H-20℃-120℃
|
1 Dome indicator
|
1 +PTM (built-in non explosion proof type)
|
|
|
|
iExiaIIBT6
|
3 M8x34L
|
3 none
|
|
L-40℃-70℃
|
|
2 +PTM (External Explosion proof Type)
|
|
|
|
pExiallCT6
|
4 M8x63L
|
|
|
|
|
3 +L/S (built-in non explosion proof type)
|
|
|
|
nNot explosion-proof
|
5 NAMUR
|
|
|
|
|
4 +L/S (external explosion-proof type)
|
|
|
|
HExdmIICT5/T6
|
|
|
|
|
|
5 +PTM+L/S (built-in non explosion proof type)
|
|
|
|
|
|
|
|
|
|
6 +PTM+L/S (external explosion-proof type)
|
|
Note: PTM represents valve position transmitter, L/S represents limit switch
|
|
Form
|
Single action
|
Double action
|
|
input signal
|
4~20 mA DC
|
|
Impedance
|
250±15 Ohm
|
|
Input pressure
|
1.4-7 kgf/ ㎠ (20-100 Psi)
|
|
trip
|
0-90°
|
|
air source interface
|
PT (NPT) 1/4
|
|
pressure gauge connection
|
PT (NPT) 1/8
|
|
power interface
|
PF 1/2 (G 1/2)
|
|
Explosion-proof rating
|
ExdmIIBT5、ExdmIICT5、ExiaIIBT6、ExiallCT6、ExdmIICT5/T6
|
|
Protection level
|
IP 66
|
|
ambient temperature
|
-20 ℃ -70 ℃ (standard type), -20 ℃ -60 ℃ (explosion-proof type)
|
|
Straightness
|
±1% F.S.
|
±2% F.S.
|
|
Lag degree
|
1% F.S.
|
|
sensitivity
|
±0.2% F.S.
|
±0.5% F.S.
|
|
Repeatability
|
±0.5% F.S.
|
|
Air consumption
|
3 LPM (Sup=1.4kgf/ ㎠, 20Psi)
|
|
Traffic volume
|
80 LPM (Sup=1.4kgf/ ㎠, 20Psi)
|
|
material
|
Die cast aluminum
|
|
weight
|
2.8kg(6.2Ib)
|