YD2110 Intelligent Power Measurement and Control Instrument I. Product Functions and Features Measurement of 34 Parameters including 3I, 3V, 3U, 3PF,
Product details
1、 Product functions and features
- Measure 34 parameters including 3I, 3V, 3U, 3PF, F, 3P, ∑ P, 3Q, ∑ Q, 3S, ∑ S, ± ∑, Wh, ± ∑ Qh, and zero line current (IO)
- V. I and F measurement accuracy ≤ 0.2%, other parameters ≤ 0.5%
- Baud rate: 300/600/1200/2400/4800/9600/19200
- Adopting DSP technology for higher accuracy, faster response, and stronger functionality
- Dot matrix LCD display, switchable interface between Chinese and English
- Capable of analyzing harmonics from 1 to 19,
- 8-channel remote signaling, 3-channel remote control, 4-channel automatic control (I, V, F, P, COS)
- Historical event recording function
2、 Technical indicators
|
Reference standards
|
GB/T13850-1998 IEC688:1992
DL/T721-2000 IEC61000-4
|
||
|
Display units
|
V/kV/MV/, A/kA,W/ kW/MW/GW,Hz, var/kvar/Mvar, VA/kVA/MVA/GVA,Wh/kWh/MWh/ varh/kvarh/Mvarh
|
||
|
accuracy
|
Voltage, current, power
|
<0.2%RD
|
|
|
Electric energy and line voltage
|
<0.5%RD
|
||
|
Frequency
|
≤0.1%RD
|
||
|
Input
|
Range
|
Voltage
|
5-120V/600V (maximum 600V)
|
|
electric current
|
0-1A/5A (maximum 6A)
|
||
|
Absorption power consumption
|
Each voltage channel
|
<0.4VA(347V)/0.2VA(150V)
|
|
|
Each current channel
|
<0.1VA(5A)
|
||
|
overload capacity
|
Voltage
|
750V continuous/1000V for 10 seconds/1200V for 3 seconds
|
|
|
electric current
|
2 times rated continuous/10 times rated 10 seconds
|
||
|
Wiring method of measurement system
|
Three phase four wire/Three phase three wire/One phase two wire or One phase three wire, etc
|
||
|
Discrete input
|
Discrete input
(Remote signaling)
|
Eight way air contact input, response time 50ms
Seven way (three way remote control, four way automatic control) relay output, normally open/normally closed dual contact output
|
|
|
Discrete output
(Remote control/self-control)
|
Contact load capacity: 5A long-term power on, adjustable outlet delay and return time
Communication method: remote control output or automatic export according to set conditions
|
||
|
Programmable settings
|
Programming mode
|
(Password)
|
|
|
Selection of measurement system
|
Three phase four wire/Three phase three wire/One phase two wire/One phase three wire, etc
|
||
|
CT, PT ratio
|
1~59999
|
||
|
Display content
|
Page change time/screen selection
|
||
|
Switching output (remote control)
|
Fixed value, delay time, and return time (overcurrent, overvoltage, undervoltage, phase failure, overvoltage, underpower, underfrequency, etc.)
|
||
|
Communication
|
Baud rate: 300/600/1200/2400/4800/9600/19200
|
||
|
Checksum
|
Odd/even/no checksum
|
||
|
Address
|
1~255
|
||
|
Time
|
Year, month, day, hour, minute, second, week
|
||
|
Electric energy accumulation reset
|
(Password)
|
||
|
Communication
|
Serial port
|
RS485 (standard)/RS232 (optional)
|
|
|
communication protocol
|
MODBUS-RTU
|
||
|
insulation strength
|
Object
|
Between input/output/power supply
|
|
|
Test Method
|
AC2kV 1-minute leakage current 2mA
|
||
|
Electromagnetic Compatibility
|
Surge
|
Power supply: 4kV (1.2 × 50 μ s) I/O line: 2kV
|
|
|
Fast transient pulse train
|
Power supply: 4kV, 2.5kHz I/O line: 2kV, 5kHz
|
||
|
Electrostatic Discharge
|
Contact discharge: 6kV Air gap discharge: 8kV
|
||
|
radiofrequency electromagnetic fields
|
Medium intensity electromagnetic radiation of 10V/m (such as handheld walkie talkies at a distance of not less than 1 meter)
|
||
|
working conditions
|
Temperature
|
-10~50℃
|
|
|
Humidity
|
20-95% (no condensation)
|
||
|
working power supply
|
power supply voltage
|
AC85-265V 50/60Hz DC85-330V (standard)
AC30-60V 50/60Hz DC18-90V (optional)
|
|
|
Total power consumption
|
<4W
|
||
|
Overall dimensions
|
Overall dimensions
|
201mm×140mm×115mm
|
|
|
Installation hole size
|
176mm×126mm
|
||