1、 Product functions and features- YThe D2050 acquisition system is composed of a host computer(YD2050)、 40 way switch quantity(YD2050-40K) and 40 current channels(YD2050-40I) Measurement module and external sensor(YComposed of D2050-50/10 or KD2050-500/10, it can simultaneously measure over 100 states and electrical parameters
- Host(YD2050) is used to measure 34 parameters of a main circuit, including 3I, 3V, 3U, 3P, ∑ P, 3Q, ∑ Q, 3S, ∑ S, F, PF, ± ∑ Wh, ± ∑ Qh, and zero line current; 40 channel switch module(YD2050-40K) can be connected to 40 switch signals and 40 current modules(YD2050-40I) can measure 40 current channels; External current sensor andYD2050-40I is compatible for use, with a maximum input current of 63A and 630A (to be ordered by the user according to actual needs)
- Adopting a dot matrix LCD display, the Chinese English interface can be switched, and all statuses and data can be output through the RS485 serial port,
2、 Technical indicators
|
Overall dimensions
|
host
|
120 mm×120 mm×139 mm
|
|
Hole: 92 mm × 92 mm
|
||
|
module
|
220 mm×125 mm×30 mm
|
|
|
External sensor (KD2050-50/10)
|
53mm×16mm×69mm
|
|
|
weight
|
host
|
750g
|
|
module
|
800g
|
|
|
External sensor (YD250-50/10)
|
59g
|
|
|
display
|
type
|
LCD
|
|
Display Pixel
|
128*64 Pots
|
|
|
Measurement
|
Suitable for 3-phase 4-wire (balanced or unbalanced), 3-phase 3-wire (balanced or unbalanced), 1-phase 3-wire, single-phase power grid
|
|
|
voltage
(True Significant Value)
|
measurement range
|
30-600V (line voltage), 20-400V (phase voltage)
|
|
PT ratio
|
1~10000
|
|
|
Continuous overload
|
800V
|
|
|
data refresh
|
2s
|
|
|
electric current
(True Significant Value)
|
measurement range
|
0~6A
|
|
Minimum measurable current
|
5m A
|
|
|
CT ratio
|
1~10000
|
|
|
Input power consumption
|
0.2VA
|
|
|
Continuous overload
|
10A
|
|
|
Impact overload
|
100A·1s
|
|
|
data refresh
|
2s
|
|
|
Expand current
(True Significant Value)
|
measurement range
|
0~63A or 0~630A
|
|
Minimum measurable current
|
50mA
|
|
|
CT ratio
|
Fixed ratio: 1 (using YD2050-50/10)
|
|
|
Maximum expandable current
|
Route 40
|
|
|
Continuous overload
|
100A
|
|
|
Impact overload
|
1000A·1s
|
|
|
data refresh
|
2s
|
|
|
Power
|
Single-phase power
|
0~4000W/var/VA
|
|
total power
|
0~12000W/var/VA
|
|
|
data refresh
|
2s
|
|
|
Frequency
|
measurement range
|
50/60Hz
|
|
data refresh
|
2s
|
|
|
power factor
|
measurement range
|
-1~1
|
|
data refresh
|
2s
|
|
|
Node 40
|
node type
|
Normally closed (alarm when open circuit)
|
|
Node power supply
|
5-12V (self powered)
|
|
|
data refresh
|
1s
|
|
|
measurement accuracy
|
current
|
0.5%(0.5~6A)
|
|
Expand current
|
0.5%(5~630A)
|
|
|
voltage
|
0.5%(20~400V)
|
|
|
power
|
0.5% (relative to U * I)
|
|
|
power factor
|
0.5%
|
|
|
frequency
|
0.1%(50/60Hz)
|
|
|
electric energy
|
1%(0.5L/0.5C)
|
|
|
auxiliary power supply
|
AC
|
85V~265V
|
|
DC
|
85V~330V
|
|
|
power consumption
|
5VA
|
|
|
insulation strength
|
Voltage input terminal
|
2.0kV
|
|
Current input terminal
|
2.0kV
|
|
|
Auxiliary power supply terminal
|
2.0kV
|
|
|
working conditions
|
Operating Temperature
|
-10~+50℃
|
|
Storage temperature
|
-25~+75℃
|
|
|
relative humidity
|
20-95% no condensation
|
|
|
Electromagnetic Compatibility
|
1.2/50-8/20us surge
|
Power supply: 4kV I/O line: 2kV
|
|
Fast transient pulse train
|
Power supply: 4kV, 2.5kHz I/O line: 2kV, 5kHz
|
|
|
Electrostatic Discharge
|
Contact discharge: 6kV Air gap discharge: 8kV
|
|
|
radiofrequency electromagnetic fields
|
Medium intensity electromagnetic radiation of 10V/m (such as handheld walkie talkies at a distance of not less than 1 meter)
|
|
|
Communication
|
interface
|
RS-485
|
|
address
|
1~247
|
|
|
Baud rate
|
1200/2400/4800/9600/19200
|
|
|
check digit
|
none
|
|
|
data bit
|
8bits
|
|
|
stop bit
|
1bits
|
|
|
communication protocol
|
ModBus RTU
|
|