technical specifications
Input: Number of channels: 5~80 channels
thermal resistance: PT100、Cu100、Cu50、BA1、BA2、G53Full range measurement, display
Display resolution of 0.1 ℃, with wire breakage recognition function
thermocouple: K. Full range measurement of S, R, B, N, E, J, T, etc. (including negative temperature), display resolution of 1 ℃ or 0.1℃, through parameter selection. Has wire breakage recognition function
DC current: 4~20mA, 0~10mA, 0~20mA display range -1999~9999, freely set range and decimal point position
DC voltage: 1-5V, 0-5V, display range -1999~9999, freely set range and decimal point position
Thermal resistance input wire resistance: within 20 Ω
Thermocouple input wire resistance: within 100 Ω
Accuracy: Using a 16 bit A/D converter
Measurement accuracy: ± 0.2% F · S
Display resolution: 1/10000
Thermocouple cold junction compensation accuracy: ± 0.2 ℃, range 0~60 ℃
Speed: up to 100ms per channel, related to Lb parameters
Display: 2-digit LED channel number display
4-digit LED measurement value display
Alarm status indicator lights and communication indicator lights for each channel
Alarm: 3 alarm modes
2-point (expandable to 4-point) common alarm relay output
Output relay contact capacity: 250VAC, 2A (resistive load)
Connect XSLCu multi-point control unit to achieve alarm output for each channel
Communication: RS232 or RS485 interface, optoelectronic isolation
Shop address 0~99 can be set
Communication rates of 2400, 4800, 9600, 19200 can be selected through setting
Supporting measurement software, providing technical support for configuration and application software
Printing: Built in hardware clock, power outage does not affect timekeeping, automatically adjusts leap year, major and minor months
Three printing startup modes: manual, manual+timed, and manual+timed+alarm
Select printing content through settings: time, alarm status, measurement value, and unit of quantity
Power Supply: V0:160VAC~26VAC,50Hz
V1:20VDC~28VDC
Environment: Temperature: 0~50 ℃ Humidity: Less than 90% RH
content |
Code and Description |
||||||||||
XSX |
Intelligent patrol detection alarm device |
||||||||||
External dimensions |
A- |
Horizontal 160 * 84 * 182 (W * H * L) |
|||||||||
B- |
Vertical 84 * 160 * 182 (W * H * L) |
||||||||||
C- |
Method 160 * 160 * 180 (W * H * L) |
||||||||||
D1- |
Desktop: 318 * 104 * 300 (W * H * L) |
||||||||||
D2- |
Disk mounted: 318 * 104 * 300 (W * H * L) |
||||||||||
Number of channels |
□□ |
Instruments with sizes A and B have a maximum of 32 channels; Instruments with dimensions of C and D have a maximum of 80 channels |
|||||||||
Input signal (other input signals, please specify when ordering) |
R |
All channels are thermal resistors, and the internal division marks of the instrument include: PT100、Cu100、Cu50、BA1、BA2、G53 |
|||||||||
E |
All channels are thermocouples, and the internal division marks of the instrument include: K、S、R、B、N、E、J、T |
||||||||||
B |
All channels have current and voltage signals ranging from 4~20mA or 1~5V. Please specify the input channel signal when placing an order |
||||||||||
X |
Input mixed use of thermistor and thermocouple |
||||||||||
L |
The input is a thermistor, thermocouple, mixed with 4-20mA, 0-10mA, 1-5V, and 0-5V. Please specify the input channels for current and voltage signals when placing an order |
||||||||||
Communication interface (independent power supply, fully isolated) |
S0 |
No communication interface |
|||||||||
S1 |
RS-232 interface |
||||||||||
S2 |
RS-485 interface |
||||||||||
Printing function (with hardware clock) |
P0 |
No printing |
|||||||||
P1 |
Split printing |
||||||||||
P2 |
Integrated printing with dimensions of D |
||||||||||
Power supply for the meter |
V0 |
220VAC |
|||||||||
V1 |
9~24VDC |
||||||||||
V2 |
other |
||||||||||
Expand alarm function |
T |
T: Indicating that there is an extended alarm function, expanding the standard 2-point to 4-point, which cannot be omitted |
|||||||||
XSX Cu interface |
C |
C: Indicates the presence of an XSL-Cu interface, not omitted |
|||||||||
Non standard functions |
N |
N: Representing non-standard functions |