XSJB series temperature and pressure compensation integrator
explain: ① Suitable for flow measurement and accumulation of superheated steam, saturated steam, and general gases that require temperature and pressure compensation ② Temperature, pressure, and flow (current, voltage, pulse) inputs, with a basic error of better than ± 0.2% F · S ③ Can display cumulative quantity, instantaneous flow rate after compensation, density, temperature, pressure, and instantaneous flow rate before compensation ④ Dimensions: 160 × 80 (horizontal/vertical), 96 × 96, ⑤ Instrument power supply 220V AC, (9~30) V DC Basic configuration: Dual display, external transmitter power supply Extended functions: ① Alarm output, up to 2 points, configurable ② Transmission output or cumulative pulse output ③ Communication interface: RS 232 or RS 485 ④ Power outage record (anti-theft function)
Model Selection Table
|
content
|
Code and Description
|
|
XSJB/
|
Dual display, external transmitter power supply
|
|
External dimensions
|
A—
|
Horizontal 160 × 80 × 125 or vertical 80 × 160 × 125
|
|
B—
|
96×96×112
|
|
Panel form
|
H
|
horizontal type
|
|
S
|
Vertical
|
|
F
|
square
|
|
Number of alarm points
|
T□
|
T0: No alarm T1~T2: 1~2 point alarm
|
|
Transmission output
(Independent power supply, fully isolated.
10 bit D/A with an error of less than ± 0.5%, or 12 bit D/A with an error of less than ± 0.2%
)
|
A0
|
no-output
|
|
A1
|
Current output (4~20) mA, (0~10) mA, or (0~20) mA
|
|
A2
|
Voltage output (0~5) V, (1~5) V
|
|
A3
|
Voltage output (0~10) V
|
|
A4
|
Other outputs
|
|
External power supply
|
B0
|
No external power supply
|
|
B1
|
External supply 24V DC, error less than ± 5%, 50mA
|
|
B2
|
Two sets of external power supplies, 24V DC and 12V DC
|
|
B3
|
other
|
|
communication interface
(Independent power supply, fully isolated, 2400~19.2K instrument address 0~99, response delay less than 500 μ s)
|
S0
|
No communication interface
|
|
S1
|
rs-232 interface
|
|
S2
|
RS-485 interface
|
|
S3
|
RS 422 interface
|
|
Printing function (with hardware clock)
|
P
|
P represents the printing interface, which can be omitted if not included
|
|
Power outage recording function
|
D
|
D means with power outage recording function, can be omitted without it
|
|
Instrument power supply
|
V0
|
220V AC
|
|
V1
|
24V DC
|
|
V2
|
12V DC
|
|
Traffic input signal
|
L1
|
Current: (4~20) mA DC, (0~10) mA DC, or (0~20) mA DC
|
|
L2
|
Voltage: (0~5) V DC, (1~5) V DC
|
|
L3
|
pulse
|
|
Temperature input signal
|
W1
|
Current: (4~20) mA DC, (0~10) mA DC, or (0~20) mA DC
|
|
W2
|
Voltage: (0~5) V DC, (1~5) V DC
|
|
W3
|
Thermal resistance: pt100 (0.0 ℃~400.0 ℃)
|
|
W4
|
Hot couple: K, T, E, S (0.0 ℃~999.9 ℃)
|
|
Pressure input signal
|
Y1
|
Current: (4~20) mA DC, (0~10) mA DC, or (0~20) mA DC
|
|
Y2
|
Voltage: (0~5) V DC, (1~5) V DC
|
|
|