1、 Product Introduction
The XSD and XSDAL series instruments display 2-4 analog inputs simultaneously, with a maximum of 4 isolated transmissions and an 8-point alarm. It can be used in conjunction with various analog output sensors and transmitters to complete physical measurements, transformations, displays, transmissions, and controls of temperature, pressure, flow rate, liquid, composition, as well as force and displacement. It has multiple calculation methods between channels, such as addition, subtraction, comparison, etc., and can transmit and alarm the calculation results.
IIselection
XSD2 series
Two measurement inputs and two independent displays.
0.2 level accuracy, measurement and control speed of 0.4 seconds (0.2 seconds x 2 channels).
■ Function for calculating and comparing the difference, sum, average, larger, and smaller values of two measurement signals.
Up to 4 alarm outputs can be set as the upper and lower limits of 2 channel measurement values or operation values.
Up to 2 transmission outputs can be set as measurement or operation values for 2 channels.
content |
Code Description |
|||||||||||
XSD2- |
2-channel input; 0.2 level measurement accuracy; Measurement and control speed 0.4 seconds (0.2 seconds/channel) |
|||||||||||
Overall dimensions |
AH |
160 × 80 × 125 hole size: 152 × 76 |
||||||||||
AS |
80 × 160 × 125 hole size: 76 × 152 |
|||||||||||
B |
96 × 96 × 112 hole size: 92 × 92 |
|||||||||||
CH |
96 × 48 × 112 hole size: 92 × 45 |
|||||||||||
CS |
48 × 96 × 112 hole size: 45 × 92 |
|||||||||||
Panel specifications |
Basic dual 4-digit LED |
|||||||||||
|
Sequential representation of input signals for two channels (Other input signals, please specify when ordering) |
E |
E |
Thermocouples (K/S/R/B/N/E/J/T); |
|||||||||
R |
R |
Thermistor (Pt100/Cu100/Cu50/BA1/BA2/G53); |
||||||||||
I |
I |
Direct current (4-20) mA, (0-10) mA, (0-20) mA; |
||||||||||
V |
V |
DC voltage (0-5) V, (1-5) V, (0-10) V; |
||||||||||
W |
W |
Potentiometer (500 Ω~10K Ω) |
||||||||||
Alarm (optional) |
T1~4 |
T3, T4 limit AH, AS, B (250V AC/3A, resistive load) |
||||||||||
|
Transmission (optional)Note ① (Resolution: 1/3000; Load Capacity: 600 Ω) Can simultaneously choose any combination of 2 channels |
A1 |
Current output: (4-20) mA, (0-10) mA, (0-20) mA. |
||||||||||
A2 |
Voltage output (1-5) V, (0-5) V |
|||||||||||
A3 |
Voltage output (0-10) V |
|||||||||||
A4 |
Voltage output (-5V~+5V) |
|||||||||||
A5 |
Voltage output (-10V~+10V) |
|||||||||||
External power supply (optional) |
B1 |
24V ± 5% below 50mA |
||||||||||
B1G |
24V ± 5% below 100mA |
|||||||||||
B2 |
12V ± 5% below 50mA |
|||||||||||
B2G |
12V ± 5% below 100mA |
|||||||||||
|
Communication (optional) (Communication rates: 2400, 4800, 9600, 19200) (Mailing address: 0-99) |
S1 |
TC ASCII protocol RS232 |
||||||||||
S2 |
TC ASCII Protocol RS485 |
|||||||||||
M1 |
Modbus RTU protocol RS232 |
|||||||||||
M2 |
Modbus RTU protocol RS485 |
|||||||||||
Printing interface (optional) |
P |
|||||||||||
Power Specifications |
V0 |
100-240V AC 50/60 Hz |
||||||||||
V1 |
10-24V AC 50/60 Hz; 10-24V DC |
|||||||||||
XSDAL series
2-4 measurement inputs, each independently displayed.
0.2 level accuracy, measurement and control speed of 0.4-0.8 seconds (0.2 seconds x number of channels).
When using 3-channel input and 4-channel input, it has three calculation methods: average, maximum, and minimum. The results of the calculation can be used for alarm, transmission, and communication.
Up to 8 alarm output points.
Up to 4 transmission outputs.
Aluminum alloy shell, pluggable terminal block.
content |
Code Description |
|||||||||||||||||
XSDAL- |
2-channel input; 0.2 level measurement accuracy; Measurement and control speed 0.6 seconds (0.2 seconds/channel) |
|||||||||||||||||
Overall dimensions |
AH |
160 × 80 × 125 hole size: 152 × 76 |
||||||||||||||||
AS |
80 × 160 × 125 hole size: 76 × 152 |
|||||||||||||||||
Panel specifications |
4-digit LED x number of channels |
|||||||||||||||||
number of channels |
2~4 |
2 to 4 channels input, standard configuration is 2 channels, additional channels are charged separately. |
||||||||||||||||
|
Sequential representation of four channel input signals (Other input signals, please specify when ordering) |
E |
E |
E |
E |
Thermocouples (K/S/R/B/N/E/J/T); |
|||||||||||||
R |
R |
R |
R |
Thermocouples (Pt100/Cu100/Cu50/BA1/BA2/G53); |
||||||||||||||
I |
I |
I |
I |
Direct current (4-20) mA, (0-10) mA, (0-20) mA; |
||||||||||||||
V |
V |
V |
V |
DC voltage (0-5) V, (1-5) V, (0-10) V; |
||||||||||||||
W |
W |
W |
W |
Potentiometer (500 Ω~10K Ω) |
||||||||||||||
Alarm (optional) |
T1~8 |
Alarm from 1 to 8 o'clock (250V AC/3A, resistive load). |
||||||||||||||||
|
Transmission (optional) (Sequential representation of 4 transmitters, write the output signal of the required number of transmitters) (Resolution: 1/3000; Load Capacity: 600 Ω) |
A1 |
A1 |
A1 |
A1 |
Current output: (4-20) mA, (0-10) mA, (0-20) mA.
|
|||||||||||||
A2 |
A2 |
A2 |
A2 |
Voltage output (1-5) V, (0-5) V |
||||||||||||||
A3 |
A3 |
A3 |
A3AA33 |
Voltage output (0-10) V |
||||||||||||||
A4 |
A4 |
A4 |
A4 |
Voltage output (-5V~+5V) |
||||||||||||||
A5 |
A5 |
A5 |
A5 |
Voltage output (-10V~+10V) |
||||||||||||||
External power supply (optional) |
B1 |
24V ± 5% below 50mA |
||||||||||||||||
B1G |
24V ± 5% below 100mA |
|||||||||||||||||
B2 |
12V ± 5% below 50mA |
|||||||||||||||||
B2G |
12V ± 5% below 100mA |
|||||||||||||||||
|
Communication (optional) (Communication rates: 2400, 4800, 9600, 19200) (Mailing address: 0-99) |
S1 |
TC ASCII protocol RS232 |
||||||||||||||||
S2 |
TC ASCII Protocol RS485 |
|||||||||||||||||
M1 |
Modbus RTU protocol RS232 |
|||||||||||||||||
M2 |
Modbus RTU protocol RS485 |
|||||||||||||||||
Printing interface (optional) |
P |
|||||||||||||||||
Power Specifications |
V0 |
100-240V AC 50/60 Hz |
||||||||||||||||
V1 |
10-24V AC 50/60 Hz; 10-24V DC |
|||||||||||||||||