Product Name: MSUQZwater level controller
Product Category: Water Level Controller
The MS-UQZ water level controller consists of three parts: magnetic levitation ball, sensor, and transmitter. When the magnetic levitation ball floats up and down along the conduit with the change of liquid level, the magnetic steel inside the float attracts the reed switch at the corresponding position in the sensor, causing the total resistance (or voltage) of the sensor to change. Then, the transmitter converts the changed resistance (or voltage) signal into a 4-20mA current signal output. And upper and lower limit alarms can be set on the display instrument to achieve positional control of the liquid level.

MS--UQZwater level controllercharacteristic:
Model number |
Specifications |
Expressing Content |
||
MS-UQZ |
|
Magnetic levitation ball liquid level transmitter |
||
|
01 |
|
|
Overhead type |
02 |
|
|
Side type |
|
03 |
|
|
Side bottom type |
|
04 |
|
|
scaffolding |
|
|
H |
|
Measurement range H |
|
|
|
|
Neck length (please specify when selecting Type 01) |
|
MS-UQZ |
|
|
|
|

MS-UQZ water level controller has four installation methods:

Zero adjustment key [Z], adjustment key [S], function key [M]
|
||
Operation content
|
Operation method
|
notes
|
Press the key to unlock
|
Press the [Z] and [S] keys simultaneously for more than 5 seconds to unlock (LCD screen displays: OPEN).
|
|
PV value reset to zero
(i.e. zero position adjustment)
|
Place the float directly on the zero position, press the key to unlock, and then press the [Z] and [S] keys simultaneously for more than 2 seconds to set the current PV value to 0 (LCD screen display: PV=0) | If the deviation between the current PV value and the 0 value exceeds 50% FS, resetting the PV value to zero is invalid (LCD screen displays: PVER) |
4mA point active migration
|
Key zeroing: Place the float in the zero position, press the [Z] key for 2 seconds, and the transmitter will output 4mA current to complete the zeroing operation. (LCD screen display: LSET) |
|
20mA point active migration
|
Button full adjustment: Place the float in the full position, press the [S] button for 2 seconds, and the transmitter outputs 20mA current to complete the full adjustment operation. (LCD screen display: HSET) |
|
Transmitter data recovery
|
Press the [Z] key first, then turn on the power, and continue to hold down [Z] for more than 5 seconds. If the LCD screen displays OK, it means that the transmitter data has been restored to the factory state. Release the key to restore it. If the LCD displays FAIL, it means that the transmitter has not been backed up and cannot be restored to the factory state. |
Display content
|
Set content
|
Operation method
|
|
0.888
ZEPO CM
|
Set 4mA point range
|
Press the [Z] key to select the modified number or decimal point | Press the [S] key to adjust the value or decimal point position |
100.00
SPRN CM
|
Set 20mA point range
|
ditto
|
ditto
|
2.000
DPMP S
|
Set damping time
|
ditto
|
ditto
|
12.008
DISP mA
|
Set display mode
|
Press the [S] key to select the display mode (displaying liquid level, current, percentage) | |
3.6
FIX C CM
|
Fixed current output
|
Output the current values displayed on the screen (3.6, 4, 8, 12, 16, 20, 22.8mA) |