Wenzhou Guoyao Electric Complete Set Co., Ltd
Home>Products>TZB/250(200).3N-H
TZB/250(200).3N-H
1. It has functions such as short circuit, overload, undervoltage, overvoltage, phase loss, zero break, and leakage protection.
Product details


TimmTZB/250.3N-HResidual current operated circuit breaker (hereinafter referred to as "protector") is the latest product developed and researched by our company to solve the problem of outdated residual current protection switches in rural power grids in China. Integrating leakage protection, automatic reclosing, overload and short-circuit protection, and load control, it has the characteristics of easy installation and reasonable structure.

This product is suitable for low-voltage distribution systems with three-phase four wire neutral point directly grounded. It is used to provide grounding fault protection for the lines, prevent equipment accidents or electrical fires caused by this, and can also be used to provide indirect contact protection for personal electric shock hazardsAnd it is widely applicable to the overall protection and line branch protection of industrial and mining enterprises, as well as the lower side of distribution transformers.This product meets the standardsGB14048.2-2008Through the state3CCompulsory Certification (Certificate Number:2010010307398955)The product is covered by quality liability insurance provided by Ping An Insurance Company of China.

Product features:

1. It has functions such as short circuit, overload, undervoltage, overvoltage, phase loss, zero break, and leakage protection.

2The leakage action value can be manually adjusted, or the leakage action value can be automatically adjusted by tracking the circuit leakage.

3The overload protection value can be adjusted according to the transformer capacity or actual load demand.

4Digital display of three-phase load current, three-phase voltage value, and line leakage current value.

5After tripping, the tripping reason and fault current can be automatically displayed.

6It has automatic and manual closing functions, making it convenient for users to use.

7When the leakage alarm function is activated, only the leakage value is displayed, and if the leakage exceeds the limit, only the alarm will be triggered without tripping.

8Built in communication interface, capable of remote control, telemetry, and remote signaling functions.

9Can query the reasons and occurrence times of previous trips (optional)

10The function of distinguishing sudden wave currents (similar to sudden waveforms of animal electric shocks) can be set. (Optional)

Technical parameters:

1Rated current100A/160A/200A/250A

2Rated voltage380V

3Rated insulation voltage400V

4Rated frequency50Hz

5Rated auxiliary power supply voltage220V

6Surge leakage action value 50 mA

7Rated residual operating current 75/100/150/200/300/500/1000mA(Adjustable)

8Rated residual non operating current 1/2In

9Rated breaking time 0.3 S、 ≤0.5 S(Adjustable)

10Minimum non driving time1In 0.13S 2In 0.06S 5In 0.05S

11Delay reclosing time20 - 60SRecloser once

12Under overvoltage action value Undervoltage ≤165V Overvoltage ≥285V

12Category of action characteristicsACtype

13Classification of Separation TimeStype

14Rated ultimate short-circuit breaking capacity(Icu)30KA

15Rated operating short-circuit breaking capacity(Ics)18KA

16Rated residual short-circuit making and breaking capacity(Im)7.5KA

17Adjustable range of load current 50250AEach level20A

Operating instructions:

1.work environment

1.1ambient temperature: -40 60

1.2relative humidity:90%

1.3altitude:2000rice

1.4pollution degree: 3level

1.5The circuit breaker should be installed in a dry, ventilated, dust-free, and free of harmful gases, away from magnetic fields and vibration. It should be vertically fixed on the distribution box or wall for easy operation.

2.Usage

2.1 Power transmission

Set the power switch of the circuit breaker to the "ON" position, the power indicator light will turn on, and the "Trip" indicator light will start flashing (indicating a closed waiting state). The electric closing mechanism of the circuit breaker will operate. When the circuit breaker is closed properly, it will be in the normal closed state, and the "Trip" indicator light will turn off.

2.2 close electricity

Set the circuit breaker [power switch] to the [off] position, trip the circuit breaker, and turn off the main circuit.

2.3Leakage over limit tripping test:

Press the 'Test' button, the circuit breaker should be able to trip, the 'Leakage Fault' indicator light should be on, the 'Trip' indicator light should be on, and the circuit breaker should be able to trip5In seconds, the 'trip' indicator light starts flashing (the electric closing mechanism is running and waiting for closing), indicating that the electric closing mechanism is in a closed state2060The automatic closing is completed in seconds. After the closing is in place, the trip indicator light and leakage fault indicator light will turn off.

2.4 Setting of leakage action value:

Manual adjustment and automatic adjustment can be selected as needed

According to the magnitude of the leakage current in the circuit, the leakage action value range of the circuit breaker can be manually set, or the leakage action value can be automatically set to levels I, II, III, and IV. According to different specifications,The leakage current of each gear corresponds to: Grade I:75mA Grade II:150mA Grade III:300mAGrade IV:500mAperhaps1000mA.

Press the 【 Set 】 key to set the gear, and press the 【 Set 】 key continuously to set the gearLevel I → Level II → Level III →Grade IV→ Class III cycle conversion; Press and holdPress the 'Settings' button for 3 seconds to enter automatic gear setting.(When)The gear indicator light is always on for a certain gear, indicating a manually set fixed gear. When the gear indicator light flashes, it indicates an automatic gear. If the circuit breaker has a gear memory function after shutting down and turning on after a power outage when in a fixed gear, the gear will remain unchanged from the original gear; If it is in automatic mode, the circuit breaker will automatically set the gear according to the leakage of the line after shutting down and turning on after power failure.

2.5This circuit breaker cannot automatically close due to overload or short circuit tripping. The power switch of the circuit breaker needs to be turned off and reconnected before power can be restored.

2.6 The auxiliary power supply used in the internal electronic circuit of this circuit breaker isNPile and5Pile, if used for three-phase power protection or specifically for single-phase protection,NThe pile must be connected to the neutral wire,5The pile must be connected to the phase line, otherwise it cannot be powered on or manually closed without leakage protection.

2.7Press and hold the [Alarm] button when power outages are not allowed or when power must be supplied due to line leakage faults during maintenance5In seconds, the alarm function is activated, and the 'Alarm Start' light is on. At this time, only the 'Leakage Fault' indicator light is on when the leakage exceeds the limit, without tripping. The use of this feature must be approved by the local power department. After entering the alarm state, press and hold the [Alarm] button again to approximately5Restore the leakage tripping function in seconds.

2.8The opening and closing indicator block is used to indicate the opening and closing status of the circuit breaker.

2.9 When the leakage tripping does not require automatic reclosing function or the internal closing motor is damaged, manual closing can be used, and a straight screwdriver can be used to press it in orderTurn the device clockwise to the closed position and stop (when the indicator block is "closed"). If manual opening is required, turn the device clockwise again to the open position and stop. If manual closing is required again, the "opening and closing switch" of the protector must be opened and closed again, and then the device must be turned clockwise to the closing state before stopping.

2.10 Digital display loop displayA□□□□B□□□□C□□□□A.□□□□B.□□□□C.□□□□L□□□□F□□□ Display as three-phase current values respectively(A)Three phase voltage value(V), and leakage current value(mA)TheLoad current control value(APress the [Function] keynumerical codemonitorDisplay the following parameters in sequence:

-AA-——Indicating leakage phase A

E005——Indicating the cumulative number of trips5order

H003——Indicating the cumulative number of tripping and locking events3order

R=03——Indicate the interruption time0.3S

d =01——Expressingmail addressset up

7b=0——Indicate surge protection settings

9H=0——Indicate the phase loss protection setting

2.11When the circuit breaker trips, the digital display will flash to show fault information

aLeakage fault tripping

Display fault current and tripping phase alternately, whileThe leakage fault and trip indicator lights are on.

Example: If L345 → - AA - is displayed, it indicates that this trip is a leakage trip, with a fault current of 345mA and A-phase leakage. If - Cd - is displayed, it indicates a surge leakage trip.

bUnder overvoltage tripping

Trip display -9Y - indicates undervoltage tripping, and the 'Trip Indicator' light is on at the same time. After the power supply voltage returns to normal, the circuit breaker automatically closes and supplies power.

cLoad control tripping

The digital display flashes and alternately displays the current values of each phase load before tripping, while the 'overcurrent fault' and 'trip indicator' lights are on.

2.12Trip record query:Press continuously[Function] key, use digitalmonitorDisplay as EXXX (XX is the number of trips), then press and hold the 【 Function 】 key for 3 seconds to increase the numbermonitorDisplay as E=XX, then press the 【 Settings 】 button to display the reason for the most recent trip. To view the next item, first press the [Function] key and then press the [Settings] key; To exit, press and hold the 【 Function 】 key for 3 seconds to activate the digital displaymonitorLXXX displays the status of all parameters normally.

2.13Breaking time setting:Press continuously[Function] key, use digitalmonitordisplay asR=03.Then press and hold the 【 Function 】 key first, and then press the 【 Settings 】 key to setR=05Change the interruption time to 0.5SFactory default is0.3S

2.14Communication address setting

Press the 【 Function 】 key continuously to activate the digital functionmonitorDisplayed as d=01. Then press and hold the 【 Function 】 key first, and then press the 【 Settings 】 key to set d=02 (03, 04).

2.15Surge protection setting

The surge protection function is turned off by default at the factory and can be turned on when needed.

Press continuously[Function] key, use digitalmonitorDisplay Tb=0, then press and hold the 【 Function 】 key, and then press the 【 Settings 】 key to set Tb=1, and the surge function will be turned on. To cancel, repeat the above steps.

2.16Phase loss protection setting

Press continuously[Function] key, use digitalmonitordisplay as9H=0.Then press and hold the 【 Function 】 key first, and then press the 【 Settings 】 key to set9H=1,The phase loss function is activated. To cancel, repeat the above steps.

2.17Load control current setting

Press the 【 Function 】 key continuously to activate the digital functionmonitorWhen displayed as FXXX, XXX represents the negative control current value. At this time, press and hold the 【 Function 】 key, and then press the 【 Settings 】 key. Each time you press the 【 Settings 】 key, the load control value changes once; Press the desired value, release the two buttons, and wait for a period of time before automatically confirming and saving.