RF admittance level switch product features:
The MK-2e RF admittance level switch has an accuracy of up to 0.5pF and high reliability
The protective performance of the internal structure of the RF admittance level switch can help eliminate erroneous signals
LED display (installed in the sensor)
● Passed safety certification and can be explosion-proof
-
MK-2eRF admittance level switchThe probe parameters are as follows:
Standard probe length: 406mm at the joint
Temperature (probe only): Fiber 232 ℃; Nylon 148 ℃
Probe material: 9.5mm diameter 316SS probe and PPS fiber and nylon insulation material protective cover
Pressure: Maximum 3.5 bar (suitable for aluminum joints)
Maximum 10 bar (applicable to 3/4'NPTSS stainless steel fittings)
Environmental temperature: -40 ℃~+65 ℃
Process temperature:<80 ℃ Aluminum material process installation (<40 ℃ environment)
<204 ℃ stainless steel material installation process (<50 ℃ environment)
Working voltage: 115VAC; 230VAC(±15%); 24VDC(±15%);
Sensitivity: 0.5pf~150pf
Accuracy: ± 0.015/° F (± 0.027 pf/℃) set at 0.5 pf
Delay: Adjustable delay within 0.25-15s
Shell: Coated with cast aluminum polyester material,
NEMA 4,IP66
Connection method: Two 3/4 "NPT connections (M20 sealed cables are required when using 1-1/2 'BSPT connection method)
Application: CSAus CSAc, CE (only for regular positions)
CSAus CSAc: Class I intrinsically safe explosion-proof (for gas)
CSAus CSAc: Class II intrinsically safe explosion-proof (for dust)