1、 Overview of LPT-S series pressure transmitters:
The LPT-S series intelligent pressure transmitter adopts a microprocessor core modular design in circuit design, which has good anti-interference performance. It is equipped with an internal temperature sensor to compensate for the transmitter, improve measurement accuracy, reduce temperature drift, and has the characteristics of good long-term stability, high reliability, and strong self diagnostic ability. Users can calibrate, set up, and configure the transmitter through the HART communication controller. The interface is designed entirely in Chinese, with different password permissions that users can easily set. Widely used in chemical, metallurgical, water conservancy, power, petroleum and other fields.
2、 Performance indicators of LPT-S series pressure transmitter:
| Measurement medium | Gas, liquid, steam | ||
| measuring range | Minimum range (kpa) | Range and Sensor Limit Values (kPa) | |
| Maximum range (URL) | Minimum Range (LRL) | ||
| 1.0 | 6.0 | -6.0 | |
| 4.0 | 40 | -40 | |
| 10.0 | 100 | -100 | |
| 12.5 | 250 | -100 | |
| 25.0 | 500 | -100 | |
| 25.0 | 1000 | -100 | |
| 87.5 | 3500 | -100 | |
| Range ratio: | 40:1 | ||
| accuracy | 0.075 level, 0.1 level (including linearity, hysteresis, and repeatability) | ||
| Range ratio impact: | 0.075 level | When the range ratio is 1:1-10:1, it is ± 0.05% of the calibrated range; | |
| When the range ratio is greater than 10:1, it is ± [0.0075 × range ratio]%; | |||
| 0.1 level, 0.2 level | When the range ratio is 1:1-10:1, it is ± 0.1% of the calibration range | ||
| When the range ratio is greater than 10:1, it is ± [0.05+0.005 x range ratio]%; | |||
| stability | 0.075 level | The error within 36 months is ± 0.15% of the maximum range | |
| 0.1 level | 36 months with an error of ± 0.2% of the maximum range | ||
| Level 0.2 | 36 months with an error of ± 0.25% of the maximum range | ||
| Temperature influence | 0.075 level | Zero or range error is ± 0.15% of the maximum range/28 ℃ | |
| 0.1 level | Zero or range error is ± 0.2% of the maximum range/28 ℃ | ||
| Level 0.2 | Zero or range error is ± 0.25% of the maximum range/28 ℃ | ||
| Power supply impact | Less than ± 0.005%/V of the calibration range | ||
| vibration effect | Less than ± 0.05%/g of the maximum range | ||
| Installation Effect | The zero drift is not greater than 0.25kPa, and this error can be eliminated by zero adjustment without affecting the range | ||
| Static pressure effect | ±0.05%URL/10MPa | ||
| output signal | 4-20mA+HART (can also have RS485) | ||
| power supply | 15-36VDC | ||
| Environmental temperature: | -40℃~85℃ | ||
| medium temperature | -40℃~120℃ | ||
| Storage temperature | -40℃~85℃ | ||
| display | 7-digit LCD display screen | ||
| protection grade | IP65 | ||
| Explosion proof grade | Exd IIC T6Gb | ||