flangedDifferential pressure transmitterIt is a differential pressure transmitter connected to the measured object in the form of a flange, used to continuously measure parameters such as liquid level, interface, and specific gravity. It can continuously measure the flow rate of liquid, steam, and gas when combined with a throttling device, and convert the measured parameter values into a unified standard pressure signal.
Parameters of single flange plug-in pressure transmitter
Measurement object: liquid level of open or sealed containers
Range: 0-2-40kPa 0-12.5~200kPa 0-50~1000kPa 0-125~2500kPa
Output: 4mA~20mA DC
Power supply: 24V DC, transmitter can operate at 12V DC without load, up to 45V DC
Communication output: Power supply voltage: 16.4V-42V DC (16.4V-30VDC intrinsic safety type)
Communication distance: 2km, when using CEV cable
Load capacitance: below 0.22 μ F
Load inductance: below 3.3mH
Distance from power cord: 15cm or more
The input impedance of the receiving instrument connected to the receiving resistor is above 10k Ω at 2.4kHz
The scale scale of the indicator (on-site) is 45mm long, with an indication accuracy of 2.5 levels (pointer type) and an indication accuracy of 0.5 levels (digital type)
Installation of explosion-proof and intrinsic safety types in hazardous areas
Regardless of the output, after positive and negative migration, the upper and lower limits of the range must not exceed the limit of the range
Maximum positive migration: 500% of the minimum calibration range
Maximum negative transfer: 600% of the minimum calibration range
Temperature range: Amplifier operating temperature -25 ℃~90 ℃ Sensor operating temperature -40 ℃~104 ℃ -18 ℃~204 ℃ Fill with inert liquid
Relative humidity: 0-100% RH
Static pressure and overpressure limit 150Ib flange: 42kPa (absolute pressure)~1.9MPa (37 ℃) 300Ib flange: 42kPa (absolute pressure)~4.9MPa (37 ℃)
Sensor variation less than 0.16cm3
Damping: The time constant is continuously adjustable between 0.2 and 1.67 seconds
Start time: 2s, no preheating required
Accuracy: ± 0.25% of the calibration range, including comprehensive errors of linearity, variation, and repeatability
Stability: ± 0.5% of maximum range (twelve months)
Communication output: Communication distance: 1.2Km (when using CEV cable) 1. 4mA~20mA DC output+fieldbus HART
Protocol communication distance: 2Km (when using CEV cable) 2. 4mA~20mA Dc output
Vibration effect: In any axial direction, at a frequency of 200Hz, the error caused is ± 0.05%/V of the maximum range
Power supply impact: less than 0.005%/V of input range
Load effect: As long as the terminal voltage of the input transmitter is higher than 12V, there is no load effect
Installation position impact: The maximum zero point error that can be generated is 0.25kPa, but it can be calibrated without affecting the range and can be eliminated through calibration.
Structural material: Isolation diaphragm: 316 stainless steel Insertion part: 316L "O" ring (in contact with measuring medium): Fluororubber
Flanges and bolts: 316 stainless steel
Filling fluid: silicone oil or inert liquid
Electrical casing: low copper aluminum alloy
Electrical shell coating: polyurethane ethylene resin baking paint
Pressure connector: High pressure side 3 "or 4", 150Ib or 300Ib flange, low pressure side flange connection thread 1/4-NPT (cone pipe thread).
Joint connection thread 1/2-NPT (this item is an optional).
Electrical connection: conduit 1/2G or M20 × 1.5 threading hole
Weight: The transmitter body weighs 4.9Kg (excluding flanges). Other technical parameters are the same as those of the WIDEPLUS LT series
Flange size and bolt hole specifications
Flange size (mm) |
Bolt hole (mm) |
||||||||
Order code |
size |
rated pressure |
outer diameter |
A |
B |
C |
number |
Hole diameter |
Hole distribution diameter |
A |
3" |
150Ib |
190.5 |
30 |
66 |
127 |
4 |
19 |
152 |
B |
4" |
150Ib |
228.6 |
30 |
89 |
157 |
8 |
19 |
190 |
C |
3" |
300Ib |
209.6 |
35 |
66 |
127 |
8 |
22.2 |
168 |
D |
4" |
300Ib |
254.0 |
38 |
89 |
157 |
8 |
22.2 |
200 |