VIP member
Fire door monitoring module (GT-FHM7100)
Fire door monitoring module (GT-FHM7100)
Product details
Connect the split door magnetic switch or electric door closer (split) to obtain the switch status of the fire door (single/double door) and feedback it to the fire door monitor; Receive the closing command from the fire door monitor to control the normally open fire door to close.
Technical parameters:
Working voltage: DC24V;
Working current: Bus working current: < 1mA;
Power supply operating current<20mA;
Bus: two-wire system (non-polar);
Encoding method: electronic encoding (address range 1-200).
Usage environment:
Temperature: -10 ℃~50 ℃
Relative humidity: ≤ 95% RH (40 ℃± 2 ℃)