Technical parameters:
Normal operating temperature |
-25 ℃~+55 ℃ (recommended) |
working temperature limit |
-40℃~+80℃ |
humidity |
Relative humidity ≤ 100%; |
atmospheric pressure |
63.0kPa~108.0kPa (altitude 4000m and below) |
Working power supply |
Rated voltage 220V ± 30%, frequency 50HZ ± 6% |
Frequency range |
50Hz, allowable deviation-6%~+2% |
External dimensions |
Width x Length x Height=112mm x 160mm x 71mm |
display |
LED indicator light |
interface type |
3 RS485 channels (1 for RS485 maintenance, 2 for meter reading, maintenance port can be set as meter reading), 1 USB, 1 modulated infrared, 1 remote communication interface |
Voltage |
Three phase four wire, 1.0 level; 3×220/380V |
Current specifications |
3 × 1 (2) A, 3 × 5 (10) A |
Frequency range |
50Hz, allowable deviation-6%~+2% |
External dimensions |
Width x Height x Thickness=180mm x 290mm x 95mm |
Meter reading and interface settings |
3-channel RS485 interface (lightning protection), 2-channel meter reading, 1-channel maintenance; |
Local settings interface |
1 infrared/TTL, 1 RS-232 interface; |
pulse output |
2 channels, with 1 active and 1 reactive; |
Clock output |
1 Road |
Remote signaling input |
4 routes, DC12V |
Door contact input circuit |
1 route, DC12V |
Switching output circuit |
4-channel, AC250V/5A DC30V/5A normally open, normally closed, non self holding output |
ALARM IN |
1 channel, AC250V/5A DC30V/5A normally open, non self holding output |
Communication sampling circuit |
1 group, three-phase three wire/three-phase four wire |
insulation voltage |
2000V |
AC sampling |
Active power level 1.0, reactive power level 2.0 |