Digital micro differential pressure transmitter
■ Range: 0-0.1mbar/0-100mbar ■ Measuring wind pressure and micro differential pressure of non corrosive gases ■ Standard industrial electrical signal
Product details
  • Product Application

    Heating, Ventilation, and Air Conditioning (HVAC)

    Energy Management System

    VAV and fan control

    Cleanroom pressure, smoke hood, and furnace ventilation control

    Static pipeline for environmental pollution control

    Pharmaceutical and 3D printing industry

    Fields such as electricity, industrial control equipment, electronics, medicine, food, environmental protection, etc

  • Technical data

    measurement range -1~1mbar,-10~10mbar-100~100mbar
    pressure unit mbar,Pa,mmH2O,inWG,mmHGdaPa
    Display Optional backlit LCD display
    signal output 4~20mA, 0~5VDC,
    0-10V DC 4-20mA+0-5/10V DC simultaneous output
    RS-485 communication (see instructions)
    output accuracy ± 1.0% FS, 0.5% FS (optional)
    output accuracy Level 0.5; 0.25 level; 0.1 level
    power supply voltage 16~30V DC
    response time 20mS, 0.5S, 1S, 2S (adjustable)
    Power consumption 1.5W
    medium temperature -10℃~60℃
    ambient temperature 200%
    Diaphragm material 316L
    Protection level IP65
    ambient temperature -20℃~85℃
    ambient humidity -10℃~70℃
    Overall dimensions 90mm × 104mm × 44.5mm (LCD display)
    97mm × 87mm × 35.5mm (without display)
    hose connector φ6.2mm
    electrical connection PG9, The maximum diameter of the cable is 8mm
    Protection level IP54
  • Instructions

    ·The standard product accuracy is 1.0% FS; special requirements can be customized with 0.5% FS. Please consult the sales engineer of Foside for details;

    ·Range selection and overload capacity refer to Table 6214-1;

    ·Equipped with LCD display, it can independently output 4-20mA, 0-5V DC, 0-10V DC, or choose to output 0-5/10V DC+4-20mA simultaneously;

    ·Without a display screen, it can output RS-485 digital signals separately, or choose to output 0-5/10V DC or 4-20mA+RS-485 digital signals simultaneously;

    ·4-20mA output is a two-wire system, 0-5/10V DC output is a three wire system, RS-485 digital signal output is a four wire system, and the combination output should be consulted with Foside sales engineers and specified during selection;

    ·The LCD display type is fixed to the mounting back panel in a rotating manner, and the mounting board is separated from the host, allowing for step-by-step installation;