Guangzhou Dongyi Automation Technology Co., Ltd
Home>Products>DC output safety barrier | 4-20mA
Firm Information
  • Transaction Level
    VIP member
  • Contact
  • Phone
    13922157087
  • Address
    Building 3, Jibang Technology Park, No. 8 Jishan New Road Street, Tianhe District, Guangzhou City
Contact Now
DC output safety barrier | 4-20mA
Brief description: FBE049 DC output safety barrier | 4-20mA safety barrier is a DC signal output isolated safety barrier that receives 4mA~20mA signal
Product details

FBE049DC output safety barrier | 4-20mASafety BarrierIt is a DC signal output isolated safety barrier that receives 4mA to 20mA signals from regulators or operators in the safety zone. Through this isolated safety barrier, it reproduces and drives intrinsically safe instruments such as electrical (I/P) converters, valve positioners, various linear actuators, and display devices in hazardous areas. Welcome to all customers.

FBE049DC output safety barrier | 4-20mASafety BarrierOverview
DC signal output isolated safety barrier receives 4mA~20mA signals from regulators or operators in the safety zone, and transmits them through this isolated safety barrier to reproduce and drive intrinsically safe instruments such as electrical (I/P) converters, valve positioners, various linear actuators, and display devices in hazardous areas.
This isolated safety barrier requires independent power supply, with electromagnetic isolation between the power supply input circuit output circuit.
Characteristics
Drive hazardous on-site intrinsic safety equipment, with a load capacity of up to 750 Ω.
4mA~20mA input, isolated output 4mA~20mA.
Modular core design, no need for zero and full adjustment.
Equipped with a working power indicator light.
Intrinsic safety input circuit [Exia IIC, input circuit overcurrent protection.
Plug and unplug terminal block, DIN rail card installation.

Product Application

1. Isolation output of analog current signal to drive on-site intrinsic safety equipment.
2. Equipment connected to the site: valve positioners, electrical converters, and other intrinsic safety display devices.
3. Location of on-site equipment: Zone 0, Zone 1, Zone 2; IIA zone, IIB zone, IIC zone; T4 to T6 danger zone.
4. Connect the safety barrier to the control system (or other unit combination instruments): The AO card of each DCS/PLC outputs current or voltage signals.

Technical Parameter

This product is an electrical interface device used to connect industrial field instruments with control room instruments. It effectively solves the interference problem of industrial automation control systems on site through reliable isolation between input output power supply, ensuring the stability and reliable operation of the system.
This product has multiple types and specifications to choose from.
Meet the functional requirements of isolation, distribution, conversion, distribution, alarm setting, etc. of various signals in the self-control system.

All internal circuits are modularized in terms of functionality.

The instrument has a card mounted structure with a flame resistant material casing and a thickness of 16, which can be densely installed and easily combined and disassembled.

Plug in terminal block, capable of live plugging.

Function: Power distribution for on-site instruments; Signal isolation transmission; Signal conversion;

Multi channel signal allocation; Alarm setting.

Number of channels: single channel; Dual channel; One in, two out; One in, three out; One in, four out.

Power supply mode: independent DC power supply; Two line power supply.

Matching signals and on-site instruments: