● Measurement: Three phase power factor ● Display: Three row digital tube (LED) display STN blue screen, wide viewing angle, high-quality, high-defini
Product details

PRODUCT MODEL | measure | display | Peripheral functions | |||
rs485 communication | analog output | Switching input | ALARM IN | |||
YN194PF-3X4 | Measurement: PF | Three rows: LED | not have | not have | not have | not have |
YN194PF-3K4 | Optional | Optional Route 1-4 AO |
Optional 1-4 DI channels |
Optional 1-4 DO routes |
||
YN194PF-3K4Y | Single row: LCD |
characteristic:
Measurement: Three phase power factor● Display: Three rows of digital tubes (LED) display STN blue screen, wide viewing angle, high-quality, high-definition LCD screen display.
Communication: RS485 communication, MODBUS-RTU protocol. It has networking communication function.
● Input: 4-channel switch input (4DI).
Output: 4-channel switch output (4DO), 4-channel analog output (4AO).
summary:
The three-phase power factor meter adopts AC sampling technology, which can measure the three-phase active power factor in the power grid. Programming and magnification can be set through panel buttons, making it highly cost-effective. It has the characteristics of easy installation, simple wiring, convenient maintenance, small engineering quantity, programmable input parameters on site, and can complete network communication of different PLCs and industrial control computers in the industry.Technical indicators:
performance | parameter | ||
transport enter measure measure apparent show |
voltage | RATING | AC500V (other specifications, please specify when ordering) |
overload | Overload: 1.2 times instantaneous: 10 times/10 seconds | ||
power consumption | < 1VA (per phase) | ||
impedance | >500KΩ | ||
accuracy | RMS measurement, accuracy level 0.5 | ||
electric current | RATING | AC5A (other specifications, please specify when ordering) | |
overload | Overload: 1.2 times instantaneous: 10 times/10 seconds | ||
power consumption | < 0.4VA (per phase) | ||
impedance | >2MΩ | ||
accuracy | RMS measurement, accuracy level 0.5 | ||
frequency | resolution | 0.01HZ | |
frequency | 45~65HZ | ||
power | accuracy | Active power accuracy level 1.0, reactive power accuracy level 1.5 | |
power supply | scope of work | AC/DC85~270V | |
power consumption | ≤5VA | ||
output | Digital Interface | RS485, MODBUS-RTU protocol | |
environment | work environment | -10~55℃ | |
Environment | -20~75℃ | ||
secure | pressure resistance | Input/power>2kV, input/output>2kV, power/output>1kV | |
isolation | Input, output, and power supply to the chassis>50M Ω |
Wiring method:

Additional features:

Example of ordering:
When signing the contract, please provide detailed information such as product model, input signal, wiring method, etc. This series of products comes with a default appearance setting as standard. If customers have special requirements, please specify them in detail in other projects.Model: YN194PF-3X4 (three-phase phase power factor meter)
Input: AC220V,/5A
Communication interface: RS485/MODBUS-RTU