At present, the requirements for water quality from all parties in China are increasing day by day, making it particularly important to choose a high-
Product details

Magnetic residual chlorine controller BC7687It can be used when the transmitter needs to add display, control, alarm, and probe automatic cleaning control functions. When PID adjustment, FFM/PWM, or current control functions need to be completed, please choose this series of instruments to expand the various functions of the transmitter. The output signal of the transmitter, 0-20mA or 4-20mA, can be transmitted to this instrument to achieve the above functions. In many cases, it is necessary to compare two sets of measurement data of the same parameter before and after the process. BC6587 and BC7687 can provide the display and control of transmitter measurement differences with identical measurement parameters and ranges. Shanghai Jingcan acts as an agent for the full line of Italian Pi Ci products, with popular products including Pi Ci TU7685 and online residual chlorine detector CL7685.

• Aquaculture • Chemical Industry • Drinking Water • Electroplating • Irrigation • Food and Beverage • Paper and Pulp • Pharmaceutical • Printing Industry • Swimming Pool

• Textile industry • Groundwater • Water treatment

● Display measurement values, with optional ranges from -9999 to 9999 corresponding

● Select the decimal point position for the displayed value

● Input current value 0/4-20mA

Can provide DC power supply for two-wire transmitters

● Single input or differential input

● Measurement units can be selected

● Set the range of measurement

● Select software filtering function

● Switch control and PID regulation function

● PFM/PWM or 4-20mA regulation control function

Two control relays are used for upper and lower limit control functions

Provide upper and lower limit alarm function for measured values

The normally open and normally closed state of the alarm relay contacts is optional

● Output range and input range linkage

● Analog output value 4-20mA/0-20mA optional

● Activate, hold, and alarm functions through two external contacts

● Automatic and manual automatic cleaning control functions

This instrument is suitable for dual channel deviation measurement and control

● Cooperate with two identical measurement signal inputs of the same range

The signal of the input 0/4-20mA transmitter is commonly used for measuring the deviation of detection values before and after the process.

range

-9999 / +9999This instrument can set the maximum and minimum values of the measuring range and the position of the decimal point arbitrarily.

Measurement unit

Users can choose one of the following suggested measurement units:%, NTU, FTU, mg/l, g/l, ppm, μ S, mS, pH, mV, or user-defined units

display

The multi line graphic display screen can display all measurement values and provide users with menu information for setting, various function settings, and other normal operation information.

key

This controller is designed with buttons that allow for direct zero and sensitivity calibration, as well as control point setting.

MODE

The instrument can be freely selected in automatic, measurement, or simulation mode, making it easy to start or maintain operations.

Two level filtering software

Users can set up two-stage filters to obtain stable readings and respond faster to changes during the measurement process.

Two analog outputs

The controller provides two analog outputs, which can correspond to any input signal. The 0/4~20mA current output can correspond to any value of the two ranges, and the analog output can also be used for PID control or measurement value transmission.

Dual on/off regulator

Two sets of relays can be set separately, and users can define their corresponding input signals and set any control point within the range.

PIDoutput

By simulating the output to complete PID control, the instrument will display the control value, and users can also choose to set any relay to FM control (pulse frequency modulation) or WM control (pulse width modulation).

call the police

This relay is used for measuring upper and lower limit alarms. When the measured value exceeds the alarm value, the relay action is triggered, and it can also be controlled through logic input.

Logic Input

Two passive input contacts can trigger a hold or alarm state.

Automatic cleaning function

There is another set of relays specifically designed to control external devices to automatically clean sensors, which can be programmed through the controller's menu.

universal power supply

85 ~264 Vac, 50/60 Hz. Other power supply options: 9~36 Vdc or 12~24 Vac, 50/60 Hz

Easy to install

All 6587 series controllers have an IP65 protection level and are suitable for wall mounted installation. They can also be used for track installation or on-site pipeline installation with corresponding installation accessories. The 7687 series provides an IP65 front protective panel and a user preferred panel mounted instrument mounting housing.

Compatibility and flexibility

This controller is compatible with all transmitters with current output in our company, and can also be used with any 0-20 mA or 4-20 mA output transmitter or sensor for all applications.

input

4-20 mA, 0-20 mA

Active or passive signal

Single or dual differential input

Power supply for passive transmitters

24Vdc (50 mA max)

midnight

±10 %Sensitivity: 12.5%~250%

resolution

1 Digital display tube

accuracy

0.2 %

repeatability

0.1 %

Nonlinear

0.1 %

Dual filtering software

0.4 ÷ 50.0Seconds are used for minimum and maximum changes

Dual channel analog output

0-20 mA / 4-20 mA Rmax 600

Dual control point HI/LO

ON/OFF - PFM - PWM, SPST relay

lag

0 ÷ 10% delay: 0 ÷ 100.0 seconds

call the police

SPDTRelay with delay of 0~100.0 seconds

Self cleaning function

Turn off/automatic cleaning/manual cleaning

SPDTRelay repetition time

0.1 ~ 100.0hour

clean time

1.0 ~ 60.0second

HOLD

0.0 ~ 20.0minute

SPSTContact with SPDT relay

220V - 5 AResistive liability

operate temperature

-10 ~ 60°C

humidity

95%No condensation

Power supply

85 ~ 264Vac - 50/60 Hz 9 ~ 36Vdc, 12 ~ 24Vac (Optional 091.42x)

Terminal Block

Plug and unplug

weight

1360 g (CL 6587) 450 g (CL 7687)

casing

ABS, IP 65

Protection level

(CL 6587)Metal, IP 65 only for front panel (CL 7687)

size

256x230x89 mm (CL 6587) 98x98x104 mm, 90x90x95mm panel opening (CL 7687)

6587Series instrument external dimensions

7687 Series instrument external dimensions

Magnetic residual chlorine controller BC7687precautions

When using this instrument, it is important to control the water flow. The pressure resistance of this probe is 10 bar (at 20 ℃), but we recommend measuring it under normal pressureQuantity. During debugging, you can slowly open the inlet valve and maintain a small amount of water flow to ensure smooth and bubble free water flow. When the incoming water pressure is too high, a pressure reducing valve must be added; When the water quality is not clean, a filtering device must be added in front of the circulation channel, as this channel is prone to blockage.During the measurement process or storage period, this electrode must not be left dry, and direct contact with the electrode tip by hand is strictly prohibited. The metal ring on the electrode tip must be bright, otherwise maintenance or consultation with the agent is required.When this electrode is temporarily out of use, please separate the electrode from the controller and store it in KCL solution or tap water (it is not recommended to store it in tap water for more than one day, and it is strictly prohibited to store the electrode in deionized water and purified water), and be careful of collision. If you need to stop storing for a long time, please contact the agent for relevant storage matters.